| Sign In | Join Free | My hardware-wholesale.com |
|
Place of Origin : China (Mainland)
Brand Name : ERFA
Certification : ISO9000
Model Number : ERFA-V12
MOQ : 1 unit
Price : Negotiated
Packaging Details : each piece with polly then 18pcs in a woodenbox with pallet
Delivery Time : 10 days after payment
Payment Terms : T/T
Supply Ability : 10000pcs per month
Rated current : 1600A 1250A
Rated duration of short-circuit : 4S
Rated peak withstand current : 60KA
Weight of movable parts : 1.4KG
Contacts limit erosion : 3MM
Certificate : ISO9000
Specification
| 1 | Rated current | A | 1600 | 1250 |
| 2 | Circuit resistance at lowest rated contact force | μΩ | ≤20 | |
| 3 | Rated short-circuit breaking current | KA | 31.5 | |
| 4 | Breaking operations of rated short circuit breaking current | Times | 50 | |
| 5 | Rated short-time withstand current | KA | 31.5 | |
| 6 | Rated duration of short-circuit | S | 4 | |
| 7 | Rated peak withstand current | KA | 60 | |
| 8 | Rated short-circuit making current | KA | 60 | |
| 9 | Rated breaking current of single capacitor bank | A | 630 | |
| 10 | Rated breaking current of back-back capacitor bank | A | 400 | |
| 11 | Rated operating sequence | O-0.3s-CO-180s-CO | ||
Mechanical data
|
Mechanical requirements
| 1 | Clearance between open contacts | mm | 11±1 |
| 2 | Average opening speed(average of first 75% of contact gap) | m/s | 1.1±0.2 |
| 3 | Average closing speed(average of last 30% of contact gap) | m/s | 0.6±0.2 |
| 4 | Rated added external contact final force | 3100±200 | |
| Added external contact force at contact touch point | N | 2200±150 | |
| 5 | Contact bouncing duration at closing operation | ms | ≤2 |
| 6 | Closing and Opening non-simultaneity of three-phase contacts | ms | ≤2 |
| 7 | Maximum Rebound during opening | mm | ≤2 |
Life
|
|
|
Electric Vacuum Interrupter 1600A 1250A For VCB Vacuum Circuit Breaker Images |